{"id":3000,"date":"2020-06-29T15:52:58","date_gmt":"2020-06-29T10:22:58","guid":{"rendered":"https:\/\/rightactionglobal.com\/?post_type=product&p=3000"},"modified":"2020-07-15T11:06:05","modified_gmt":"2020-07-15T05:36:05","slug":"aw-aio2188-in-addressable-input-module","status":"publish","type":"product","link":"https:\/\/rightactionglobal.com\/product\/aw-aio2188-in-addressable-input-module\/","title":{"rendered":"AIO2188-IN Addressable Input Module"},"content":{"rendered":"

The AW -AIO2188-IN Intelligent input module (AW-AIO2188-IN module for short) is used with AW -AFP2188,a two-bus fire alarm control panel. It can be connected with a conventional smoke detector, a conventional heat detector, a conventional manual call point, a conventional hooter\/horn and some other equipment.<\/p>\n

After the said equipment starts to operate, the alarm signal output will be sent by the AW-AIO2188-IN module to the fire alarm control panel through a signal bus to give a fire alarm.<\/p>\n

\n
\n

Features:<\/strong><\/p>\n

    \n
  1. Mode of operation: Nonpolar two-wire system;<\/li>\n
  2. Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection status or remain lit in the operation status;<\/li>\n<\/ol>\n

    Parameters:\u00a0<\/strong><\/p>\n

    \n
    \n
      \n
    1. Quiescent current: \uff1c0.5mA (bus); \uff1c6mA (power line);<\/li>\n
    2. Action current: \uff1c2mA (bus); \uff1c15mA (power line);<\/li>\n
    3. Operating environment: Temperature: \uff0d 10 \u2103 \uff5e 50 \u2103 ; relative humidity: \u2264 95% (40 \u2103 \u00b1 2 \u2103 , without condensation);<\/li>\n
    4. Terminal load: 4.7K resistance;<\/li>\n
    5. External dimensions: 86\u00d786\u00d740(mm);<\/li>\n
    6. Weight: about 119g.<\/li>\n<\/ol>\n<\/div>\n<\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"

      The AW -AIO2188-IN Intelligent input module (AW-AIO2188-IN module for short) is used with AW -AFP2188,a two-bus fire alarm control panel. It can be connected with a conventional smoke detector, a conventional heat detector, a conventional manual call point, a conventional hooter\/horn and some other equipment. After the said equipment starts to operate, the alarm signal<\/p>\n","protected":false},"featured_media":3001,"template":"","meta":[],"product_cat":[505,744],"product_tag":[],"_links":{"self":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product\/3000"}],"collection":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media\/3001"}],"wp:attachment":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media?parent=3000"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_cat?post=3000"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_tag?post=3000"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}