{"id":2994,"date":"2020-06-29T15:45:38","date_gmt":"2020-06-29T10:15:38","guid":{"rendered":"https:\/\/rightactionglobal.com\/?post_type=product&p=2994"},"modified":"2020-07-15T11:11:07","modified_gmt":"2020-07-15T05:41:07","slug":"aw-amc2188-addressable-manual-call-point","status":"publish","type":"product","link":"https:\/\/rightactionglobal.com\/product\/aw-amc2188-addressable-manual-call-point\/","title":{"rendered":"AMC2188 Addressable Manual call point"},"content":{"rendered":"
\n

The AW -AMC2188 addressable manual call point (manual call point for short) is mainly designed to be used with an intelligent two-bus control panel. If it is pressed after a fire is manually confirmed, an alarm signal may be sent to a fire alarm control panel which will, after receiving the alarm signal, display the coded address and the equipment status of the manual call point.<\/p>\n

When the manual call point is operating normally, the red indicator will blink; when there is a fire alarm, it will remain lit. The manual call point supports electronic coding and has a built-in fire telephone jack and a PHONE indicator, making its engineering application convenient.<\/p>\n

Features:<\/strong><\/p>\n

    \n
  1. It can realize complete electronic coding and in situ rewriting with help of a coder.<\/li>\n
  2. Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently.<\/li>\n
  3. It is designed with a two-wire fire telephone jack and is therefore more applicable to engineering application.<\/li>\n
  4. Designed with passive output contacts, it can control other external equipment directly through an intermediate relay.<\/li>\n
  5. The pressing sheet on the manual call point will not get crushed after it is pressed, but can be reset by a special tool, so it can be used repeatedly.<\/li>\n<\/ol>\n<\/div>\n
    \n

    Parameters:\u00a0<\/strong><\/p>\n

    \n
    \n
      \n
    1. Operating voltage: 24V (pulse modulation);<\/li>\n
    2. Operating current: \uff1c300uA (in the monitoring status); \uff1c2mA (in the action status);<\/li>\n
    3. Output contact: Normally open contact; capacity: 0.1A\/30VDC;<\/li>\n
    4. Weight: About 120g;<\/li>\n
    5. Wiring method: nonpolar two-bus system (L1, L2);<\/li>\n
    6. Operating environment: Indoor, temperature: \uff0d10\u2103\uff5e\uff0b50\u2103; relative humidity: \u226495% (40\u2103\u00b12\u2103, without condensation);<\/li>\n
    7. Coding method: It can realize online coding with the help of a coder and without the necessity of disassembling the bus (however, the equipment must be powered off). Address codes 1 to 324 are available for selection;<\/li>\n
    8. Telephone jack: Two-wire fire telephone jack (equipped with a standard \u00a0\u04246.3 single-track audio connector);<\/li>\n
    9. Starting part: A plastic pressing sheet that may be used repeatedly. It can be manually reset with a special tool after being pressed;<\/li>\n
    10. Starting mode: Press the pressing sheet manually;<\/li>\n
    11. Indicator: The red ALARM indicator will blink in the inspection status or remain lit in the alarm status; the PHONE indicator will blink when a fire telephone loop is connected, otherwise it will be out;<\/li>\n
    12. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).<\/li>\n<\/ol>\n<\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"

      The AW -AMC2188 addressable manual call point (manual call point for short) is mainly designed to be used with an intelligent two-bus control panel. If it is pressed after a fire is manually confirmed, an alarm signal may be sent to a fire alarm control panel which will, after receiving the alarm signal, display the<\/p>\n","protected":false},"featured_media":2995,"template":"","meta":[],"product_cat":[505,745],"product_tag":[],"_links":{"self":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product\/2994"}],"collection":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media\/2995"}],"wp:attachment":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media?parent=2994"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_cat?post=2994"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_tag?post=2994"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}