{"id":2075,"date":"2020-05-29T12:11:35","date_gmt":"2020-05-29T06:41:35","guid":{"rendered":"https:\/\/rightactionglobal.com\/?post_type=product&p=2075"},"modified":"2022-10-07T12:17:25","modified_gmt":"2022-10-07T06:47:25","slug":"addressable-repeater-for-fire-alarm-system","status":"publish","type":"product","link":"https:\/\/rightactionglobal.com\/product\/addressable-repeater-for-fire-alarm-system\/","title":{"rendered":"Addressable Repeater for fire alarm system RP2188"},"content":{"rendered":"

The AW-RP2188 fire display panel (display panel for short) is a kind of microprocessor-controlled fire display panel developed by our company. Each display panel is connected to a fire alarm control panel produced by our company via a special RS-485 interface to process and display the data sent from the fire alarm control panel. Each floor of a building may have a display panel installed. When there is a fire alarm on the floor where the display panel is installed, or the neighboring floor above or below it, the display panel will give a horn\/strobe alarm and display the floor No., the room No., and some other position information of the fire alarm.<\/p>\n

 <\/p>\n

Addressable Fire Alarm Repeater Feature:<\/strong><\/h2>\n
    \n
  1. Each display panel is connected with a fire alarm control panel via a RS-48 bus. At most 99 display panels may be connected with each RS-485 bus.<\/li>\n
  2. The display panels can display fire alarm messages or feedback messages only rather than fault messages, action messages or other messages.<\/li>\n
  3. A fire alarm control panel may be used for setting the display area of a display panel. The set display panel can display the fire alarm messages of the designated area (floor display) only. Note: See the User\u2019s Manual of the fire alarm control panel for the setting method.<\/li>\n
  4. It can replace a AW-AFP2100 fire display panel in a 2100 system.<\/li>\n<\/ol>\n

    Addressable Fire Alarm Repeater\u00a0Technical parameters:<\/strong><\/h2>\n
      \n
    1. Executive standard: General Technical Conditions for Fire Indicating Panels (GB17429-1998)<\/li>\n
    2. Display capacity: Each display panel can display the fire alarm messages of floors -10~90 and at most 99 fire alarm messages or feedback messages.<\/li>\n
    3. Wiring system: Four-wire system, power lines (+24V, GND) and RS485 signal lines (485A, 485B);<\/li>\n
    4. Operating environment: Indoor; temperature: -10\u2103\uff5e+50\u2103; relative humidity: \u226495% (40\u2103, without condensation);<\/li>\n
    5. Power supply: DC 24V \u00b120 %;<\/li>\n
    6. Overall power consumption: \uff1c3W;<\/li>\n
    7. Contact capacity: Relay dry contacts, normally open or normally closed, capacity: 1.25A\/DC30V (resistive load).<\/li>\n<\/ol>\n","protected":false},"excerpt":{"rendered":"

      The AW-RP2188 fire display panel (display panel for short) is a kind of microprocessor-controlled fire display panel developed by our company. Each display panel is connected to a fire alarm control panel produced by our company via a special RS-485 interface to process and display the data sent from the fire alarm control panel. Each<\/p>\n","protected":false},"featured_media":2076,"template":"","meta":[],"product_cat":[505,744],"product_tag":[],"_links":{"self":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product\/2075"}],"collection":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media\/2076"}],"wp:attachment":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media?parent=2075"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_cat?post=2075"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_tag?post=2075"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}