{"id":2061,"date":"2020-05-28T15:27:13","date_gmt":"2020-05-28T09:57:13","guid":{"rendered":"https:\/\/rightactionglobal.com\/?post_type=product&p=2061"},"modified":"2022-10-07T12:17:25","modified_gmt":"2022-10-07T06:47:25","slug":"lpcb-addressable-fire-alarm-system-32-zone-control-panel","status":"publish","type":"product","link":"https:\/\/rightactionglobal.com\/product\/lpcb-addressable-fire-alarm-system-32-zone-control-panel\/","title":{"rendered":"LPCB Addressable fire alarm system 32 zone control panel FP300"},"content":{"rendered":"
The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.<\/div>\n
The AW-FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable points and expansion capabilities. It is compatible with other peripherals made by ASENWARE with its own protocol.<\/div>\n
<\/div>\n
\n

Addressable fire alarm system\u00a0AW-FP300 Features\uff1a<\/strong><\/h2>\n
The AW-FP300 single loop 32 zone fire alarm control panel offers the following features:<\/div>\n
1. Up to 324 addresses on one loop<\/div>\n
2. An easy to read, 4.3” color screen LCD with a resolution of 480\u00d7272<\/div>\n
3. Zone indication and control panel(ZCP) for 32 zones gives a quick indication of the location of an alarm<\/div>\n
4. Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation<\/div>\n
5. An independently programmable conventional sounder circuit output<\/div>\n
6. Integral power supply and battery<\/div>\n
7. Integral printer<\/div>\n
8. Flexible and intuitive cause and effect programming on front panel<\/div>\n
9. Zone test, point test and module start\/stop testing facilitate the commissioning<\/div>\n
10. U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance<\/div>\n
11. Hierarchy management with three access levels<\/div>\n
12. Anti-tamper protection by a key lock<\/div>\n
13. CAN bus for interconnection of up to 20 FACPs and RS485 for connection with up to 30 fire indicating panels per FACP<\/div>\n<\/div>\n
<\/div>\n
\n

Addressable fire alarm panel Technical parameters\uff1a<\/strong><\/p>\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n
\u00a0Power supply\u00a0<\/strong><\/td>\n<\/tr>\n
Mains supply<\/td>\n230VAC (-15%, +10%). 47 ~\u00a063Hz. Max current 0.8A<\/td>\n<\/tr>\n
Mains fuse<\/td>\nT3.15AL250V<\/td>\n<\/tr>\n
Operating voltage<\/td>\n18.5 ~\u00a030VDC<\/td>\n<\/tr>\n
Recommended mains cable<\/td>\nScreened or standard\/black mains cable, cable size 0.75mm2<\/td>\n<\/tr>\n
Power rating<\/td>\nImax.a=1.2A; Imax.b=2.6A; Imin=0.65A<\/td>\n<\/tr>\n
Max. charging current<\/td>\n1.2A<\/td>\n<\/tr>\n
Max. battery supply current<\/td>\n4A (when the Mains is disconnected)<\/td>\n<\/tr>\n
Battery capacity, type and recommended model<\/td>\nMax. capacity 2\u00d712V\/17Ah; Min. capacity 2\u00d712V\/12Ah
\nVRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic)<\/td>\n<\/tr>\n
Max. internal resistance of battery<\/td>\n1.5\u03a9<\/td>\n<\/tr>\n
Battery fuse<\/td>\nF8AL250V<\/td>\n<\/tr>\n
Recommended battery cable<\/td>\n14AWG<\/td>\n<\/tr>\n
Quiescent current (full loaded)<\/td>\n< 0.4A<\/td>\n<\/tr>\n
Outputs\u00a0<\/strong><\/td>\n<\/tr>\n
S.C. Out (+, -)<\/td>\nOutput voltage<\/td>\n18.5 ~\u00a030VDC<\/td>\n<\/tr>\n
Max. output current<\/td>\n0.5A<\/td>\n<\/tr>\n
Fuse rating<\/td>\nF1AL250V<\/td>\n<\/tr>\n
End of line resistor<\/td>\n4K7<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nPlain unscreened cable, 1.5mm2<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~2mm2<\/td>\n<\/tr>\n
Transmission distance<\/td>\n\u22641500m<\/td>\n<\/tr>\n
Max. number of sounders @50mA<\/td>\n20<\/td>\n<\/tr>\n
F.P.E. Out (+, -)
\nF.A. Out (+, -)<\/td>\n
Output voltage<\/td>\n18.5 ~\u00a030VDC<\/td>\n<\/tr>\n
Max. output current<\/td>\n0.5A<\/td>\n<\/tr>\n
Fuse rating<\/td>\nF1AL250V<\/td>\n<\/tr>\n
End of line resistor<\/td>\n4K7<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nPlain unscreened cable, 1.5mm2<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~2mm2<\/td>\n<\/tr>\n
Transmission distance<\/td>\n\u22641500m<\/td>\n<\/tr>\n
Fault Out
\n(NC, COM, NO)<\/td>\n
Contact capacity<\/td>\n30VDC@2A, 125VAC@0.5A<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nPlain unscreened cable, 1.5mm2<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~\u00a02mm2<\/td>\n<\/tr>\n
24VK (+, -)<\/td>\nOutput voltage<\/td>\n18.5 ~\u00a030VDC<\/td>\n<\/tr>\n
Max. output current<\/td>\n0.6A<\/td>\n<\/tr>\n
Fuse rating<\/td>\nF1AL250V<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nPlain unscreened cable, 1.5mm2<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~2mm2<\/td>\n<\/tr>\n
Input\u00a0<\/strong><\/td>\n<\/tr>\n
Class change (+, -)<\/td>\nInput mode<\/td>\nPassive<\/td>\n<\/tr>\n
Cable resistance<\/td>\n\u2264500\u03a9<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nPlain unscreened cable, 1.5mm2<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~2mm2<\/td>\n<\/tr>\n
Loop\u00a0<\/strong><\/td>\n<\/tr>\n
Loop Out (+, -)
\nLoop In (+, -)<\/td>\n
Output voltage<\/td>\n16.5 ~\u00a030VDC, pulse<\/td>\n<\/tr>\n
Output current<\/td>\n0 ~0.3A<\/td>\n<\/tr>\n
Loop type<\/td>\nClass A<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nScreened or unscreened twisted-pair, 1.5mm2<\/td>\n<\/tr>\n
Transmission distance<\/td>\n\u22641000m<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~2mm2<\/td>\n<\/tr>\n
Network communication\u00a0<\/strong><\/td>\n<\/tr>\n
RS-485<\/td>\nMax. number of FIPs<\/td>\n30<\/td>\n<\/tr>\n
Transmission rate<\/td>\n9600 bps<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nScreened or unscreened twisted-pair, 1mm2<\/td>\n<\/tr>\n
Transmission distance<\/td>\n\u22641000m<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~5mm2<\/td>\n<\/tr>\n
CAN<\/td>\nMax. number of panels<\/td>\n20<\/td>\n<\/tr>\n
Transmission rate<\/td>\nOptional: 10K, 20K, 50K and 100K bps<\/td>\n<\/tr>\n
Recommended type of cable<\/td>\nScreened or unscreened twisted-pair, 1mm2<\/td>\n<\/tr>\n
Transmission distance<\/td>\n\u22641000m<\/td>\n<\/tr>\n
Cable diameter<\/td>\n1mm2 ~5mm2<\/td>\n<\/tr>\n
Physical dimensions\u00a0<\/strong><\/td>\n<\/tr>\n
Approx. Dimensions of the panel (W\u00d7H\u00d7D)<\/td>\n430\u00d7560\u00d7170mm<\/td>\n<\/tr>\n
Approx. weight (without battery)<\/td>\n14kg<\/td>\n<\/tr>\n
Operating conditions\u00a0<\/strong><\/td>\n<\/tr>\n
Temperature range: 0\u00b0C~45\u00b0C; Max relative humidity: 95% (40\u00b0C \u00b12\u00b0C, no condensation)<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n","protected":false},"excerpt":{"rendered":"

The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance. The AW-FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable<\/p>\n","protected":false},"featured_media":2062,"template":"","meta":[],"product_cat":[505,744],"product_tag":[],"_links":{"self":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product\/2061"}],"collection":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/types\/product"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media\/2062"}],"wp:attachment":[{"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/media?parent=2061"}],"wp:term":[{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_cat?post=2061"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/rightactionglobal.com\/wp-json\/wp\/v2\/product_tag?post=2061"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}